4BU5495-0AR08-0F
TR PN(KVA):60 UPRI(V):400 USEC(V):400+/-

From SIEMENS

POWER TRANSFORMER; PHASES:3; PN(KVA):60; UPRI(V):400; USEC(V):400+/-5%; ISEC(A):82,5-86,6-91,2; UK(%):3,39; F(HZ):50...60; VECTOR GR./SHIELD WNG.:DYN5 /0; TA/ISOKL:55 /H; IP20; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; VDE 0532
General technical data
Product designationpower transformer
Product brand nameSIDAC
Operating apparent output rated valueV·A60 000
Efficiency0.96
Connection method for transformersDyn5
Certificate of suitabilityCE
Product function
Temperature monitoringNo
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Relative short-circuit voltage%3.39
Inputs
Phase number of the inputs3
Input voltage
_1 rated valueV400
Electrical input frequency
minimumHz50
maximumHz60
Outputs
Phase number of the outputs3
Output voltage
_1 rated valueV420
_2 rated valueV400
_3 rated valueV380
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions
Thermal class acc. to IEC 60085H
Ambient temperature rated value°C55
Protection class IPIP20
Mechanical data
Type of electrical connection
at output for main current circuitscrew-type terminals
at input for main current circuitscrew-type terminals
Mounting typescrews
Construction form of the iron core3UI 305/125
Certificates/ approvals

External links