4BU5495-0AL40-0F TR PN(KVA):70 UPRI(V):480-460-440 USEC(V
From SIEMENS
TRANSFORMER; PHASES:3; PN(KVA):70; UPRI(V):480-460-440; USEC(V):220; ISEC(A):183,7; F(HZ):60...60; VECTOR GR./SHIELD WNG.:DYN5 /0; TA/ISOKL:55 /H; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; VDE 0532 | |||
General technical data: | |||
Product designation | transformer | ||
Product brand name | SIDAC | ||
Operating apparent output rated value | V·A | 70 000 | |
Efficiency | 0.96 | ||
Connection method for transformers | Dyn5 | ||
Certificate of suitability | CE | ||
Product function | |||
Temperature monitoring | No | ||
Insulation monitoring | No | ||
Short-circuit and overload proof | No | ||
Number of shielding windings | 0 | ||
Relative short-circuit voltage | % | 3.1 | |
Inputs: | |||
Phase number of the inputs | 3 | ||
Input voltage | |||
_1 rated value | V | 480 | |
_2 rated value | V | 460 | |
_3 rated value | V | 440 | |
Electrical input frequency | |||
minimum | Hz | 60 | |
maximum | Hz | 60 | |
Outputs: | |||
Phase number of the outputs | 3 | ||
Output voltage | |||
_1 rated value | V | 220 | |
Electrical output frequency | |||
maximum | Hz | 60 | |
minimum | Hz | 60 | |
Ambient conditions: | |||
Thermal class acc. to IEC 60085 | H | ||
Ambient temperature rated value | °C | 55 | |
Protection class IP | IP00 | ||
Mechanical data: | |||
Type of electrical connection | |||
at output for main current circuit | screw-type terminals | ||
at input for main current circuit | screw-type terminals | ||
Mounting type | screws | ||
Construction form of the iron core | 3UI 305/125 |