4AV2302-2EB00-0A
POWER SUPPLY; PHASES:1;

From SIEMENS

POWER SUPPLY; PHASES:1; PN(KW):0,084; UPRI(V):230-115; USEC(V DC):24; ISEC(A DC):3,5/4,2 (60/40 CEL); F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; PROTECTION CL.:I; TA/ISOKL:60 /B; W(%):5; IP00; TYPE OF TERMINALS:SCREW/TAB CONNECTION; INSTALLATION:MOUNTING RAILS; EN 61558-2-6, EN61131-2 >SAFETY ISOLATING TRANSFORMER<
General technical data:
Product designation
Product brand nameSIDAC
Vector groupIi0
Certificate of suitabilityCE / cRUus
Product function
Temperature monitoringNo
Insulation monitoringNo
Short-circuit and overload proofYes
varistor protective wiringYes
Operating resource protection classI
Number of shielding windings0
Inputs:
Phase number of the inputs1
Type of current of the inputsAC
Input voltage
_1 rated valueV230
_2 rated valueV115
Electrical input frequency
minimumHz50
maximumHz60
Input voltage
minimumV103.5
maximumV243.8
Input current
_1 rated valueA0.63
_2 rated valueA1.3
Type of electrical connection at input for main current circuitscrew-type terminals / tab terminals
Outputs:
Type of current
_1 at outputDC
Output voltage
_1 rated valueV24
Output voltage of the measurement signal at analog output at DC maximumV28.8
Output voltage of the measurement signal at analog output at DC minimumV20.4
Output current
_1 rated valueA3.5
Type of electrical connection at output for main current circuitscrew-type terminals / tab terminals
Relative residual ripple
of the output voltage 1 for main current circuit maximum%5
Ambient conditions:
Thermal class acc. to IEC 60085B
Ambient temperature rated value°C60
Protection class IPIP00
Mechanical data:
Mounting typestandard rail
Construction form of the iron coreEI 66-88/41
Widthm72
Heightm136
Depthm111

External links